GOLDAIR Module OUT69 SC2
Application
The OUT69 SC2 motor protection module has been especially
developed to monitor motor winding temperature on scroll
refrigeration compressors.
Mainly used for Copeland compressors.
Application
The OUT69 SC2 motor protection module has been especially
developed to monitor motor winding temperature on scroll
refrigeration compressors.
Mainly used for Copeland compressors.
Technical specifications
Supply voltage : AC50Hz 115-230V, AC60Hz 120-240V -15%...+10% 3VA
AC50/60Hz 24V -15%...+10% 3VA
Permitted ambient temperature : -30...70℃
Temperature measuring circuits
- Type : PTC, acc.to DIN44081/082
- Number of sensors : 1...9 serial
- R25,total : <1.8 KΩ
- Measurement voltage : ≤2.5V(acc.to IEC 60034-1)
Time delay : 30min±5min
Output relay : Max AC 240V 2.5A C300
AgNi 90/10 : Min. AC/DC>24V, >20mA
Mechanical service life : Approx. 1 million switching cycles
Protection class acc. to En 60529 : IP00
Connection : 6.3mm FASTON connectors
Housing material : PA66
Mounting : Screw mounted
Dimensions in mm : 76.5x81.5x34.5
Weight : approx.200g
Voltage : Order No.
-115-230VAC : 16G08 SC2 00
-24VAC : 16G08 SC2 01